HEPA and ULPA Filter Integrity Testing Using DOP or PAO

DOP and PAO testing checks whether an installed HEPA or ULPA filter system is leak-tight and continuing to perform as intended.

The test does not only assess the filter media. It can identify leakage through:

  • Filter media: Damage, pinholes or weaknesses within the filter itself.
  • Gaskets and seals: Gaps allowing contaminated air to bypass the filter.
  • Filter frames: Poor seating, deformation or incorrect installation.
  • Housings and joints: Leakage around the installed filter system.

During the test, a controlled aerosol challenge is introduced upstream of the filter. A calibrated aerosol photometer is then used downstream to detect penetration and locate any leakage.

The terms DOP test, PAO test and filter integrity test are often used interchangeably. DOP describes the established test method, while PAO and products such as Ondina are commonly used as the aerosol challenge during modern testing.

Velocity Safety provides in-situ filter integrity testing for cleanrooms, local exhaust ventilation systems, spray booths, negative pressure units, portable dust extractors and other HEPA- or ULPA-filtered equipment.

Our service includes:

  • Upstream aerosol challenge generation.
  • Downstream photometer scanning or sampling.
  • Checks across the filter media, seals, gasket and housing.
  • Identification and location of penetration or bypass leakage.
  • Comparison against the applicable test method and acceptance criteria.
  • A traceable digital DOP or PAO test report.

Book DOP / PAO Filter Integrity Testing

Quick Answer: What is a DOP test?

A DOP test is an in-situ filter integrity test used to identify leaks in installed HEPA and ULPA filtration systems. A controlled aerosol is introduced upstream of the filter, and a calibrated photometer checks downstream for penetration through the filter media, seals, gasket or housing.

Although the term “DOP testing” is still widely used, modern testing commonly uses PAO or another suitable aerosol rather than the original DOP substance.

Examples of in situ filters we test:

  • Portable dust extractors (Vacs/Vacuums) L, M and H Class
  • Fixed dust extraction units found on fixed machinery.
  • Filters in Local Exhaust Ventilation (LEV) systems
  • Fume cupboards/cabinets
  • Spray booths
  • Clean rooms
  • Negative Pressure Units (NPU’s)
  • Air Scrubbers
  • Air Cleaners
  • Air movers
  • Other units that have an in situ filter installed.

DOP Testing, PAO Testing and HEPA Integrity Testing Explained

These terms are closely related, but they do not all describe exactly the same thing.

Term Meaning How It Is Used
DOP test The established industry term for aerosol-based in-situ filter integrity testing. Still commonly used when referring to HEPA and ULPA leak testing, even where a different aerosol is used.
PAO test An integrity test using polyalphaolefin aerosol as the upstream challenge. Commonly used as an alternative to the original DOP aerosol.
Ondina test An integrity test using a suitable Ondina oil aerosol. Frequently used for filter integrity testing in the UK and Europe.
HEPA or ULPA integrity test The broader description of the test’s purpose: confirming that the installed filtration system has no unacceptable leakage. May use PAO, Ondina or another suitable challenge aerosol depending on the system and test procedure.

Velocity Safety confirms the appropriate aerosol, test method and acceptance criteria before testing begins.

When Is DOP or PAO Filter Integrity Testing Required?

The appropriate testing frequency depends on the equipment, application, exposure risk, manufacturer instructions and the examination or validation programme applying to the system.

Filter integrity testing may be required:

  • Before first use: To confirm that a newly installed filter and its housing are leak-tight.
  • After filter replacement: To identify damage, poor seating or leakage around the gasket or frame.
  • During periodic examination or validation: At the interval established by the risk assessment, applicable guidance or site procedure.
  • After repairs or relocation: Where work could have affected the filter, housing, seals or surrounding system.
  • Following suspected damage: Including impact, incorrect handling, visible defects or loss of containment.
  • Where system performance changes: For example, unexplained contamination, abnormal pressure readings or reduced extraction performance.

Portable dust extraction equipment and negative pressure units used in higher-risk environments may require testing at comparatively short intervals. Installed cleanroom, LEV and process filtration systems should follow the applicable validation programme, COSHH assessment, manufacturer guidance and site-specific risk.

Where a HEPA filter forms part of an LEV control system, filter integrity testing may be completed alongside the system’s thorough examination and test. However, the required integrity-test interval should be determined for the specific equipment rather than applying one universal frequency to every HEPA or ULPA filter.

HSE confirms that on-tool extraction is a form of LEV and requires thorough examination and testing, while the standard LEV interval is generally at least every 14 months unless a shorter statutory interval applies.

Our DOP / PAO Testing Process – Certified, Compliant, Safe

HEPA and ULPA filters aren’t “fit and forget” – they must be verified in use. Here’s how our integrity testing works:

1. Pre-Test Checks & Risk Review

We inspect filter housings, review safe access, and ensure conditions are suitable for testing – including isolation if required.

2. Upstream Aerosol Injection

A certified aerosol generator disperses Ondina oil upstream of the filter at a controlled concentration. This acts as the challenge.

3. Downstream Leak Detection

Using a calibrated aerosol photometer, we scan the downstream face of the filter or exhaust to detect any penetration leakage.

4. Full System Validation

We assess not just the media, but also seals, frames, and gaskets – identifying installation or mechanical failures.

5. Certification & Report Delivery

You receive a detailed integrity test certificate, with results referenced to BS EN 1822 and ISO 14644-3 – ideal for audits and site logs.


If your filter fails, we’ll flag the issue and advise on resealing, replacement, or system improvement.

Get a Free Quote

Why choose Velocity Safety Ltd

Why choose Velocity Safety Ltd for your filter integrity testing requirements

  • Manufacturer trained in filter testing to BS EN 1822.
  • Our engineers also hold the BOHS W501 measurement of hazardous substances occupational hygiene qualification.
  • Over 12 years experience in the health and safety industry.
  • We use calibrated and serviced aerosol photometers with traceable certification.
  • Our reports meet the requirements of BS EN 1822-1, BS EN ISO 29463 & BS EN 14644.
  • Able to demonstrate our advice follows and is in accordance with:
    – BS EN 1822-1:2019 – High Efficiency air filters (EPA, HEPA and ULPA) – Part 1: Classification, performance testing and marking.
    – BS EN ISO 14644-3 – Clean rooms and associated controlled environments – Test Methods
  • Fully Insured

What Others Say About Us…

Cleanroom managers and paint booth operators value our attention to detail and the confidence our testing brings.

Who Our DOP & PAO Filter Integrity Testing Is For

Not every filter sits in a cleanroom. From NPUs on asbestos sites to spray booths and dust extraction systems, HEPA and ULPA filters are everywhere – and every one of them needs proof it’s doing its job. Velocity Safety provides DOP and PAO integrity testing for any environment where clean, compliant air matters.

Cleanroom & Pharmaceutical Facilities

Precision validation for HEPA and ULPA filters used in controlled environments – ensuring full compliance with ISO 14644 and BS EN 1822 standards.

Book Cleanroom Filter Testing

Hospitals, Laboratories & Research Centres

Protect critical spaces and staff with verified HEPA integrity testing and full traceable documentation for audits and regulators.

Book HEPA Integrity Testing

Spray Booth & Paint Shop Operators

Confirm spray booth extraction filters are capturing hazardous overspray and vapours effectively, keeping COSHH compliance intact.

Schedule Spray Booth Testing

Asbestos & Dust Removal Contractors

Six-monthly DOP testing for H-Class vacuums, NPUs, and air movers used in asbestos removal and dust control – as required under COSHH Reg.9.

Arrange NPU & Vacuum Testing

Manufacturing & Engineering Workshops

Verification of fixed LEV and process extraction filters to ensure airborne contaminants are contained before reaching workspaces.

Book Workshop Filter Testing

Facilities & Estate Managers

Portfolio-wide testing and certification for installed air systems across commercial or industrial estates – ideal for audit or insurance compliance.

Book Multi-Site Testing

Construction & Refurbishment Sites

Testing for temporary NPUs and negative pressure units to ensure on-site dust and fume control systems perform as specified.

Book Site Filter Test

Universities & Education Labs

Protect research staff and students with certified HEPA filter testing for laboratory and workshop extraction systems.

Book Laboratory Filter Test

Healthcare & Dental Practices

Ensure air purification and local extraction systems meet infection-control requirements and audit expectations.

Book Healthcare Filter Testing

Not sure if your site falls under these categories? Give us a call – we’ll talk it through in plain English.

Call us

Other Services Available:

FAQs – DOP / Filter Integrity Testing

Filter testing is critical for compliance in high-risk environments. Here’s what clients often ask us:

What is DOP testing?

DOP testing is the widely used name for an in-situ filter integrity test carried out on installed HEPA or ULPA filtration systems.

A controlled aerosol is introduced upstream of the filter, and a calibrated photometer checks downstream for penetration through the filter media, seals, gasket or housing.

What does DOP stand for?

DOP originally referred to dioctyl phthalate, the aerosol substance historically used for filter testing.

The term “DOP test” remains common within industry, although modern integrity testing frequently uses PAO, Ondina or another suitable challenge aerosol instead.

What does PAO stand for?

PAO stands for polyalphaolefin.

PAO can be generated as an aerosol upstream of an installed filter so that a photometer can detect any penetration or leakage downstream.

Is DOP testing legally required?

COSHH Regulation 9 requires engineering controls used to control exposure to hazardous substances to be maintained and thoroughly examined and tested at suitable intervals.

Where a HEPA or ULPA filter is critical to the performance of that control, an integrity test may form part of the evidence needed to confirm that the system remains effective. The exact test method and frequency depend on the equipment, risk assessment, applicable standards and industry requirements.

Is DOP testing the same as PAO testing?

They describe the same general type of aerosol-based filter integrity test, but DOP and PAO are not the same substance.

“DOP testing” is often used as the generic industry name for the method, while PAO is one of the aerosols commonly used during modern testing.

What is a DOP test used for?

A DOP test is used to identify unacceptable leakage in an installed HEPA or ULPA filter system.

It can detect defects within the filter media and leakage around seals, gaskets, frames and housings that may allow contaminated air to bypass the filter.

What is a PAO filter integrity test?

A PAO filter integrity test introduces a controlled polyalphaolefin aerosol upstream of the filter and measures penetration downstream using a calibrated photometer.

The purpose is to confirm that the installed filtration system remains leak-tight and suitable for its intended application.

What is the difference between filter integrity and filter efficiency testing?

Filter integrity testing checks an installed filter system for localised leaks through the media, seals, gasket, frame or housing.

Filter efficiency testing determines the overall filtration performance or classification of a filter under a defined test method. An in-situ DOP or PAO test should not automatically be treated as a complete factory efficiency-classification test.

Which filters can be DOP or PAO tested?

Velocity Safety tests installed HEPA and ULPA filters used in cleanrooms, LEV systems, negative pressure units, air scrubbers, spray booths, fume cupboards and suitable portable dust extraction equipment.

Testing feasibility depends on having an appropriate aerosol injection point, airflow conditions and safe downstream access.

Can you test HEPA filters in cleanrooms?

Yes. We provide in-situ HEPA and ULPA filter integrity testing for cleanrooms and associated controlled environments.

The test method and acceptance criteria are agreed according to the facility, validation requirements and applicable standards, including BS EN ISO 14644-3 where relevant.

Can you test H-Class vacuums and portable extraction units?

Yes. We test suitable H-Class vacuums, portable dust extractors, air scrubbers, negative pressure units and other mobile HEPA-filtered equipment.

The equipment must provide safe access for aerosol introduction and downstream measurement.

How often should DOP testing be carried out?

The required interval depends on the filter application, level of risk, manufacturer instructions, equipment history and applicable examination or validation programme.

Testing should also be considered after initial installation, filter replacement, repairs, relocation, suspected damage or an unexplained change in system performance.

Does the equipment need to be shut down for DOP testing?

The system normally needs to operate under controlled test conditions so that the challenge aerosol can pass through the filter and be measured downstream.

Parts of the process or surrounding work area may need to be isolated for safety, but the exact arrangement depends on the equipment and testing procedure.

What happens if a HEPA filter fails the integrity test?

The location and level of leakage will be recorded, and the affected system should not be assumed to provide its intended containment until the issue has been resolved.

Corrective work may involve reseating the filter, repairing or replacing seals, addressing housing leakage or replacing the filter. The system should then be re-tested before being returned to normal use.

What information is included in a DOP test report?

The report may include the equipment and filter identification, test location, aerosol used, instrument details, upstream challenge concentration, downstream readings, leakage locations, acceptance criteria and overall result.

Any failures or remedial recommendations will also be clearly recorded.

Do you provide DOP and PAO testing nationwide?

Yes. Velocity Safety provides mobile DOP, PAO and HEPA filter integrity testing throughout the North West and across the wider UK.

We support cleanrooms, laboratories, healthcare sites, workshops, spray booths, construction projects and organisations managing filtered equipment across multiple locations.

Can filter integrity testing be combined with LEV testing?

Yes. Where the filter forms part of a local exhaust ventilation system, integrity testing can often be coordinated with the system’s LEV thorough examination and test.

Combining the work can reduce repeat site access and provide a clearer assessment of the extraction system and its filtration performance.

Whatever your filter integrity test requirements are you can be sure you’re in honest, reliable and safe hands.

Contact Velocity Safety today 01254 933 486 or Contact Us

Schedule DOP Filter Testing

Confirm your HEPA filters are fit for purpose. Our integrity testing service (DOP/PAO) ensures critical systems in cleanrooms, labs and spray booths meet required containment standards.

    01254 933 486
    info@velocitysafety.co.uk

    Velocity Safety
    Unit 7 Whitebirk Enterprise Centre,
    Lower Phillips Road
    Blackburn,
    Lancashire
    BB1 5UD